Co-production with a gas engine driven heat pump in Tønder

A gas engine driven heat pump unit in Tønder is expected to begin co-production of cooling and district heating in November 2017. Heat is supplied to the local district heating company, Tønder Fjernvarmeselskab, and cooling is supplied to the local company SAPA Extrusion. Previously, the heat production in Tønder was based solely on natural gas boilers.

Description

The heat pump unit consist of two parallel mechanical heat pumps driven by either natural gas engines or an electrically powered engine, depending on the present economic conditions. Depending on the cooling needs at SAPA, the heat pumps can be driven by either ambient air or cooling water from SAPA. Using ambient air with a temperature of 7°C, the thermal capacity of the gas engine is 4.3 MW and for the electric motor it is 3.3 MW. By using more than one heat source, the heat pump investment is more robust, in the case of SAPA withdrawing their cooling needs. However, the two heat sources enable the heat pumps to operate with a larger heat pump capacity, compared to sole utilization of excess heat from SAPA.

Tønder Fjernvarmeselskab has approximately 2700 consumers connected to the district heating network and the annual heat production is currently 92,000 MWh. The annual heat production from the heat pumps, using ambient air, is expected to be at least 36,100 MWh, corresponding to nearly 40 % of the total heat deliverance. If cooling water from SAPA is to be used, the potential is larger, as the efficiency of the heat pumps would increase. Water from SAPA can be delivered with a temperature of approximately 20 ◦C, which is cooled to a temperature between 6 and 10°C. When using the gas engine, the heat pumps are basically natural gas boilers with average annual efficiencies above 200 %.

In addition to the heat pumps, an accumulation tank has been established to store cold water, ensuring the supply for SAPA. The heat produced cannot be stored, meaning that the heat pumps must deliver supply temperatures around 70°C directly to the district heating network. Nonetheless, the heat pumps decrease the amount of natural gas used at the district heating company. Simulations predict annual savings between € 725,000 and € 950,000, depending on the natural gas price. If the gas price increase, the savings increase as well.

While SKAT, the Danish Customs and Tax Administration, which is Denmark’s tax authority, have stated, that the heat is not excess heat, co-production is still used to exploit an industrial heat source and thus resembling reuse of heat from an urban source.

Facts about this case

Installed heat capacity: 4.3 MW gas and 3.3 MWelectric
Heat source: Process cooling (20 °C) and air
Heat pump COP: 2.16 using air and 2.9 using excess heat P
roduction: 40 % of the total heat production in Tønder can be produced by the heat pump (based on air)
Temperatures: Excess heat is deliveres to the heat pump at approximately 20 °C
CO2-savings: Above 4000 ton CO2 annually
Investment cost: € 4.92 M (does not include necessary investments for SAPA Extrusion)
Savings: Between € 725,000 and € 950,000 annually
Period: Finished in 2017
District heating network: 2700 consumers
Link to web page: http://www.tonder-fjernvarme.dk/
 
Contact information:
Johnny Pedersen, Tønder Fjernvarmeselskab
A.m.b.a., +45 7472 2801, [email protected]